G5TUPS40 MGE Galaxy 5000 40 kVA UPS System Call for Price
Description

G5TUPS40 Technical Specifications

MGE Galaxy 5000 40 kVA UPS System

Output
Max Configurable Power (Watts): 36.0kWatts / 40.0kVA
Neutral Output Current: 87A
Output Voltage Note: Configurable for 380, 400, or 415 V 3 Phase nominal output voltage.
Output Voltage Distortion: Less than 2%
Output Frequency (sync to mains): 50 Hz – programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8%, 60 Hz
Other Output Voltages: 208, 220, 380, 400, 415, 600
Topology
Double Conversion Online
Waveform Type: Sine wave
Overload Operation: 10 minutes @ 125% and 60 seconds @ 150%
Maximum Output Current: 190A
Output Voltage THD: < 1% linear load and < 2.5% nonlinear load
Bypass
Internal Bypass (Automatic and Manual), Optional External Bypass
Input
Input Frequency: 45 – 65 Hz
Input Voltage Range for Main Operations: 340 – 460 (400V), 408 – 538V
Input Total Harmonic Distortion: Less than 3% for full load
Type of Input Protection Required: 3-pole breaker
Maximum Short Circuit Withstand (Icw): 20.0kAmps
Input Power Factor at Full Load: 1.0
Batteries & Runtime
Battery Type: No internal battery – uses external battery system
Efficiency
View Efficiency Graph
Communications & Management
Control Panel: Multi-function LCD status and control console
Emergency Power Off (EPO): Optional

Reviews (0)
Ratings

0.0

0 Product Ratings
5
0
4
0
3
0
2
0
1
0